IEC Electrical | 75 | 150 | 275 | 320 | 385 | 440 | |
Nominal AC Voltage (50/60Hz) | Uo/ Un | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V |
Maximum Continua Operating intentione (AC) | Uc | 75 V | 150 V | 275V | 320 V | 385 V | 440 V |
Nominale Dimissionem Current (8/20 μs) | In | 10 KA | 10 KA | 10 KA | 10 KA | 10 KA | 10 KA |
Maximum munus Current (8/20 μs) | Imax | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA |
Voltage Praesidium Level | Up | 0.2 kV | 0.6 kV | 1.3 kV | 1.5 kV | 1.5 kV | 1.8 kV |
Responsio tempus | tA | < 25 ns | |||||
Retro-Sursum Fuse (max) | 125 A gl/gG . | ||||||
Brevis Circuitus Current Rating (AC) | ISCCR | 10 KA | |||||
TOV resiste 5s | UT | 90V | 180V | 335V | 335V | 335V | 580V |
TOV 120min | UT | 115V | 230V | 440V | 440V | 440V | 765V |
modus | resistere | resistere | Tutus Fail | Tutus Fail | Tutus Fail | Tutus Fail | |
Mechanica & Environmental | |||||||
Temperature Range operating | Ta | -40ºF ad +58ºF [-40ºC ad +70ºC] | |||||
Licet operating Umor | RH | 5%...95% | |||||
Atmosphaerae pressura et altitudo | 80k Pa ... 106k Pa / -500 m......2000 m | ||||||
Terminatio stupra Torque | Mmax | 39.9 Ibf ·in [4.5 Nm] | |||||
Conductor Cross Section (max) | 2 AWG (Solidus, Stranded) / 4 AWG (flexibile) | ||||||
35 mm2 (Faxum, Stranded) / 25 mm2(Faxum) | |||||||
Adscendens | 35 mm DIN Rail, EN 60715 | ||||||
Gradus Praesidium | IP 20 (instructum) | ||||||
habitationi Material | Thermoplastic: Extinguere Degree UL 94 V-0 | ||||||
Scelerisque Praesidium | Ita | ||||||
Operans rei publicae / culpae indicium | Viridi ok / Rubrum defectus | ||||||
Contactus remoti (RC) RC Switching CapacityRC Conductor Cross Section (max) | OptionalAC: 250V/0.5 A;DC: 250V / 0.1 A;125V / 0.2 A;75V / 0.5 A16 AWG (Solidus) / 1.5 mm2(Solidus) |
Focus ad solutiones mong pu per 5 annos parandas.